Modelo de inversor
HSPH220KH
A 220 kW HOBER solar pumping inverter for a trifásico AC pump on a 380/400/440 V supply. Para estações de bombeamento e fornecimento de projetos, em que o inversor é entregue como painel de comando.
160–250 kW · IP21
What this model is
HSPH220KH is a solar pumping inverter for a 220 kW trifásico AC pump: not a pump and not a panel, but the drive that stands between the two. The array’s DC comes in, the drive holds the array at its maximum power point, and what leaves it for the pump is AC at the voltage and the frequency the motor was built for. The frequency follows the array rather than a fixed supply, so the pump turns at the speed the sun can pay for at that moment, and the day’s water is pumped while the sun is up. This model also states an AC input: grid or generator is switched in while solar is low, and switched out again as solar recovers. Nothing is stored in a battery: the energy is stored as water in a tank or a reservoir.
An existing 220 kW AC pump does not have to be replaced to run on solar. It needs the right drive in front of it, and HSPH220KH is that drive: the motor, the pipework and the wiring stay where they are.
For this model the datasheet states an array window of 400V minimum Vmp and 900V maximum Voc, 506A of rated input current over one string, MPPT at up to 99%, an output of 380/400/440 V at 50-60 Hz (support program range 15 to 60Hz) and an IP21 enclosure for an indoor installation with the switchgear.
What that buys is a pumping day with no meter running: the fuel bill or the grid bill that used to arrive with every hour of pumping goes, and the pump that was already paid for keeps working. The array is not guessed either: the array window is what the string has to sit inside, and the sizing is read from the pump’s duty point rather than from a rule of thumb.
To confirm this model against your pump, send the nameplate details — power, voltage, phase and rated current — and we check them against this model’s own figures before anything is ordered. The code to quote is HSPH220KH.
Where it sits in the range
Control cabinet · three-phase 380/400/440 V · 160–250 kW pump output · IP21
Para estações de bombeamento e fornecimento de projetos, em que o inversor é entregue como painel de comando.
The whole inverter range The series this model belongs to
Other models in this family
The datasheet for this model
Every row is a row of the source datasheet, read from this model’s own column, in the sections and the order the source prints them. A row the source does not state for this model carries an em dash rather than a figure borrowed from the model beside it.
Solar Panel DC Input
| Parâmetro | HSPH220KH |
|---|---|
| Max Voc Voltage | 900V |
| Min Vmp Voltage | 400V |
| Recommend Vmp Voltage | ≥500V (Only Solar), ≥560V (Hybrid Power) |
| Max MPPT Efficiency | 99% |
| Rated Input Current | 506A |
| Number of Strings | 1 |
| Note | Automatic. MPPT Function to Identify the Voc and Vmp of Solar Panel, without programming |
Hybrid AC/Generator Input
| Parâmetro | HSPH220KH |
|---|---|
| Voltage | 3 Phase 380/400/440V |
| Related Input Current | 410A |
| Hybrid Mode | Automatic. AC supplement automatic while solar is in low power mode and AC disconnect automatic while solar power recovery |
AC Output (For Pump, Rerator, Fan Parameters)
| Parâmetro | HSPH220KH |
|---|---|
| Max Adapted AC Pump Horse Power | 293HP |
| Max Adapted AC Pump Power | 220KW |
| Drive Mode | 3Phase Variable Frequency Drive |
| Max Output Voltage | 380/400/440V |
| Max Output Frequency | 50-60 Hz (support program range 15 to 60Hz) |
| Max Output Current | 426A |
| Max Efficiency | 99% |
| Water Level Sensor (Borehole / Tank) | Yes |
| 4G/WiFi Module | YES (Optional) |
| Support Remote Monitoring & Control System (SPMCS) | Yes |
| Display | LCD Size: 1024×600 7" Resistive touch screen Display Information, Curve Display, Multi Language, parameters setting, time calibrate, update, Error history |
| Others Input / Output | 4-20mA input 2 channel (can for water level sensor, max support 200meter) 0-5V input 1 channel Output dry point for RUN/STOP 1 channel Low power protection 1 channel Inverter Power 1 channel |
| Waterproof | IP21 |
| Noise | <75dB |
| Cooling Method | Force Cooling by Fan |
Operating Environment
| Parâmetro | HSPH220KH |
|---|---|
| Operating Environment Temperature | -10 to 60°C; above 60°C need to derate load |
| Max Humidity | 95%RH |
| Using Altitude | <3000m; above 3000m need to derate load |
| Installation Restrictions | Direct sunlight, thick dust, corrosive gas or oil mist, flammable gas, liquid, etc. |
Modelo de inversor
Order HSPH220KH
Send the pump nameplate details and we confirm this model, the array it needs and the supply it expects.